AirGuard GT Series

Product Name:AirGuard GT Series
Product Model:RF51050*,RF51051*,RF51052*,RF51053*,RF51054*,RF51055*,RF51
Updated:2009.12.03
Views:32

AirGuard GT Series
Maximum discharge current
20kA (8/20μs)
Maximum power rating (VSWR)
1.25:1 or 1.20:1
Frequency Range
DC to 2.5GHz
Peak Pulse Current (8/20μs)
40kA
Impedance
50 Ω
Temperature Range
-40°F to +194°F
-40°C to +90°C
Dust & Waterproof
IP67
Salt Fog
MIL-STD-202-101 D/B
Temperture Shock
MIL-STD-202-107 D/B-1
Vibration
MIL-STD-202-204 D/D
Shock
MIL-STD-202-213/A
Model | Connectors | Frequency Range(GHz) |
VSWR | Insertion Loss (dB) |
Peak Pulse Current (8μs x 20μs) |
Impedance (Ω) |
RF51050* | BNC(f) Bulkhead to BNC(f) | DC - 2.5 | 1.25:1 | 0.1 | 40kA | 50 |
RF51051* | BNC(m) to BNC(f) | DC - 2.5 | 1.25:1 | 0.1 | 40kA | 50 |
RF51052* | TNC(f) Bulkhead(f) to TNC(f) | DC - 2.5 | 1.25:1 | 0.1 | 40kA | 50 |
RF51053* | TNC(m) to TNC(f) | DC - 2.5 | 1.25:1 | 0.1 | 40kA | 50 |
RF51054* | N(f) Bulkhead to N(f) | DC - 2.5 | 1.20:1 | 0.1 | 40kA | 50 |
RF51055* | N(m) to N(f) | DC - 2.5 | 1.20:1 | 0.1 | 40kA | 50 |
RF51057* | SMA(m) to SMA(f) | DC - 2.5 | 1.20:1 | 0.2 | 40kA | 50 |
RF51058* | N(f) Bulkhead to SMA(f) | DC - 2.5 | 1.20:1 | 0.2 | 40kA | 50 |
* Add alpha suffi x to identify gas-tube voltage: A = 90V, B = 145V, C = 230V, D = 350V, E = 470V, F = 600V, G = 800V, H = 1,000V
Gas-Tube Voltage (Voltage should be defi ned by maximum RF power)
Parameter | Gas-Tube Voltage | |||||||
Voltage Code | A | B | C | D | E | F | G | H |
Gas-Tube Voltage Rating | 90 | 145 | 230 | 350 | 470 | 600 | 800 | 1000 |
Maximum RF Watts See notes 1, 2, 3 | 37 | 96 | 241 | 558 | 1006 | 1640 | 2915 | 4555 |
kA Transient Current for 8 x 20μs pulse | 40 | 40 | 40 | 40 | 40 | 40 | 30 | 20 |
V dynamic at 5k/μs | 600 | 600 | 650 | 800 | 1200 | 1500 | 1900 | 2200 |
Let-through Energy in mJ see notes 1 & 4 | 0.3 | 0.3 | 0.35 | 0.7 | 2.2 | 4.4 | 9 | 14 |
Note 1: Data given for 50Ω systems. For 75Ω systems multiply by 0.67, for 90Ω systems multiply by 0.55.
Note 2: For combined carrier applications the sum of all peak RF voltages plus any injection voltages should not exceed 60% of the Gas-Tube voltage rating. Peak RF volts = 1.4 x (RF power x Ohms) ^0.5.
Note 3: RF power is limited by the connector capability also.
Note 4: Let-through Energy based on the 6kV/3kA per ANSI C62.41.

Brackets
Model | Connectors | Diameter |
RF51075 | N | 0.630” (1.6cm) |
RF51077 | BNC/TNC | 0.505” (1.28cm) |